 Michael, Bart, all:

I took a look at the littlefuse catalog this A.M. and vitrually every fuse
in it (fast or slow blow) is listed to hold 135% of the rated current for
as much as 1 hour. At 140% the time would be somewhat less, but still many
minutes. How long did you leave it run at 42 A?

- Mike

> It's the fuses not blowing which raises the questions.
> Bart